1. Water chiller manufacturers-Hope Deepblue Interlock mechanical & electrical anti-freezing system: multi anti-freezing protection
The coordinated anti-freezing system features following merits: a lowered primary sprayer design for the evaporator, an interlock mechanism which links the secondary sprayer of evaporator with the supply of chilled water and cooling water, a pipe blockage prevention device, a two-hierachy chilled water flow switch, an interlock mechanism designed for the chilled water pump and cooling water pump. Six levels anti freezing design ensures timely detection of break, underflow, low temperature of chilled water, automatic actions will be taken to prevent tube freezing.
2. Water chiller manufacturers-Hope Deepblue Auto purge system combining muti-ejector&fall-head technology: speedy vacuum purging and high vacuum degree maintenance
This is a new, high efficiency automatic air purge system. The ejector functions as a small air extraction pump. DEEPBLUE automatic air purge system adopts multiple ejectors to increase the air extraction and purge rate of chiller. Water head design can help to evaluate vacuum limits and maintain a high vacuum degree. The design with features rapidly and highness can provide a high vacuum degree for every part of chiller at any time. Therefore, oxygen corrosion is precluded, service life time is prolonged and optimal operating status is maintained for chiller.
3. Water chiller manufacturers-Hope Deepblue Simple and reliable system pipe design: easy operation and reliable quality
Maintainable structure design: spray plate in absorber and spray nozzle in evaporator are replaceable. Ensure capacity will not drop in lifespan. No solution regulation valve, refrigerant spray valve and high pressure refrigerant valve, so the leakage points are less, and unit can keep stable operation without manual regulation.
4. Water chiller manufacturers-Hope Deepblue Automatic anti-crystallization system combining potential difference-based dilution and crystal dissolution: eliminate crystallization
A self-contained temperature & potential difference detection system enables chiller to monitor excessively high concentration of the concentrated solution. On one hand upon detecting an overly high concentration the chiller automatically feeds refrigerant water to concentrated solution for dilution, on the other hand, the chiller utilizes HT LiBr solution in generator to heat concentrated solution to a higher temperature. In the event of a sudden power failure or abnormal shutdown, potential difference-based dilution system will start rapidly to dilute LiBr solution and to ensure rapid dilution after power supply recovers.
4. Water chiller manufacturers-Hope Deepblue Unique solution circulation volume control technology
The control system (AI, V5.0) employs an innovative ternary control technology to adjust circulated solution volume. Traditionally, only parameters of generator liquid level are used to control of solution circulation volume. This new technology combines merits of concentration & temperature of concentrated solution and liquid level in generator. Meanwhile, an advanced frequency–variable control technology is applied to solution pump to enable chiller to achieve an optimal circulated solution volume. This technology improves operating efficiency and reduces start-up time and energy consumption.
5.Cooling water temperature control technology
The control system (AI, V5.0) can control and adapt heat source input according to cooling water inlet temperature changes. By maintaining cooling water inlet temperature within 15-34 ℃, chiller operate safely and efficiently.
6.Solution concentration control technology
The control system (AI, V5.0) uses a unique concentration control technology to enable real-time monitoring/control of concentration and volume of concentrated solution as well as heat source input. This system can maintain chiller under safe and stable at high concentration condition, improve chiller operating efficiency and prevent crystallization.
7.Intelligent automatic air extraction function
The control system (AI, V5.0) can realize real-time monitoring of vacuum condition and purge out the non-condensable air automatically.a
8.Integral sintered sight glass: a powerful guarantee for high vacuum performance
The leakage rate of the whole unit is lower than 2.03X10-9 Pa.m3 /S , Which is 3 grade higher than national standard, can ensure unit's lifespan.
Unique surface treatment for heat exchange tubes: high performance in heat exchanging & less energy consumption
The evaporator and absorber have been hydrophilic treated to ensure even liquid film distribution on tube surface. This design can improve heat exchange effect and lower energy consumption.
9.Li2MoO4 Corrosion inhibitor: an environment –friendly corrosion inhibitor
Lithium Molybate (Li2MoO4), an environment-friendly corrosion inhibitor, is used to replace Li2CrO4 (Containing heavy metals) during the preparation of LiBr solution.
10.Frequency control operation: an energy-saving technology
Chiller can adjust its operation automatically and maintain optimal working according to different cooling load.
11.Plate heat exchanger: saving more than 10% energy
A stainless corrugated steel plate heat exchanger is adopted. This type of plate heat exchanger has a very sound effect, a high heat recovery rate and remarkable energy saving performance. Meanwhile, the stainless steel plate has a service life of over 20 years.
1.Fully-automatic control functions
The control system (AI, V5.0) is featured by powerful and complete functions, such as one-key start up/ shutdown, timing on/off, mature safety protection system, multiple automatic adjustment, system interlock, expert system, human machine dialogue(multi languages), building automation interfaces, etc.
2.Complete chiller abnormality self-diagnosis and protection function.
The control system (AI, V5.0) features 34 abnormality self-diagnosis & protection functions. Automatic steps will be taken by system according to level of an abnormality. This is intended to prevent accidents, minimize human labor and ensures a sustained, safe and stable operation of hot water absorption chiller.
3.Unique load adjustment function
The control system (AI, V5.0) has a unique load adjustment function, which enables automatic adjustment of hot water absorption chiller output according to actual load. This function not only helps to reduce startup/shutdown time and dilution time, but also contributes to less idle work and energy consumption.
8.Unique dilution stop control
This control system (AI, V5.0) can control operation time of different pumps required for dilution operation, according to concentrated solution concentration, ambient temperature and remaining refrigerant water volume. Therefore, an optimal concentration can be maintained for the chiller after shutdown. Crystallization is precluded and chiller re-start time is shortened.
9.Working parameter management system
Through interface of this control system (AI, V5.0), operator can perform any of following operations for 12 critical parameters relating to chiller performance: real-time display, correction, setting. Records can be kept for historical operation events.
10.Chiller fault management system
If any prompt of occasional fault is displayed on operation interface, this control system(AI, V5.0) can locate and detail fault, propose a solution or trouble shooting guidance. Classification and statistical analyses of historical faults can be conducted to facilitate maintenance service provided by operator
11.Remote Operation & Maintenance System
Deepblue Remote Monitoring Center collects the data of the units distributed by Deepblue around the world. Through the classification, statistics, and analysis of real-time data, it displays in the form of reports, curves, and histograms to achieve an overall overview of equipment operating status and fault information control. Through a series of collection, calculation , control, alarm, early warning, equipment ledger, equipment operation and maintenance information and other functions, as well as customized special analysis and display functions, the remote operation, maintenance, and management needs of the unit are finally realized. The authorized client can browse the WEB or APP, which is convenient and fast.
Model | RXZ(95/85)- | 35 | 58 | 93 | 116 | 145 | 174 | 233 | 291 | 349 | 465 | 582 | 698 | 756 | |
Cooling capacity | kW | 350 | 580 | 930 | 1160 | 1450 | 1740 | 2330 | 2910 | 3490 | 4650 | 5820 | 6980 | 7560 | |
104 kCal/h | 30 | 50 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 650 | ||
USRT | 99 | 165 | 265 | 331 | 413 | 496 | 661 | 827 | 992 | 1323 | 1653 | 1984 | 2152 | ||
Chilled water |
Inlet/outlet temp. | ℃ | 12→7 | ||||||||||||
Flow rate | m3/h | 60 | 100 | 160 | 200 | 250 | 300 | 400 | 500 | 600 | 800 | 1000 | 1200 | 1300 | |
Pressure drop | kPa | 70 | 80 | 80 | 90 | 90 | 80 | 80 | 80 | 60 | 60 | 70 | 80 | 80 | |
Joint connection | DN(mm) | 100 | 125 | 150 | 150 | 200 | 250 | 250 | 250 | 250 | 300 | 350 | 400 | 400 | |
Cooling water |
Inlet/outlet temp. | ℃ | 32→38 | ||||||||||||
Flow rate | m3/h | 113 | 188 | 300 | 375 | 469 | 563 | 750 | 938 | 1125 | 1500 | 1875 | 2250 | 2438 | |
Pressure drop | kPa | 65 | 70 | 70 | 75 | 75 | 80 | 80 | 80 | 70 | 70 | 80 | 80 | 80 | |
Joint connection | DN(mm) | 125 | 150 | 200 | 250 | 250 | 300 | 350 | 350 | 350 | 400 | 450 | 500 | 500 | |
Hot water | Inlet/outlet temp. | ℃ | 95→85 | ||||||||||||
Flow rate | m3/h | 38 | 63 | 100 | 125 | 156 | 188 | 250 | 313 | 375 | 500 | 625 | 750 | 813 | |
Pressure drop | kPa | 76 | 90 | 90 | 90 | 90 | 95 | 95 | 95 | 75 | 75 | 90 | 90 | 90 | |
Joint connection | DN(mm) | 80 | 100 | 125 | 150 | 150 | 200 | 250 | 250 | 250 | 300 | 300 | 300 | 300 | |
Power Demand | kW | 2.8 | 3 | 3.8 | 4.2 | 4.4 | 5.4 | 6.4 | 7.4 | 7.7 | 8.7 | 12.2 | 14.2 | 15.2 | |
Dimension | Length | mm | 3100 | 3100 | 4120 | 4860 | 4860 | 5860 | 5890 | 5920 | 6920 | 6920 | 7980 | 8980 | 8980 |
Width | mm | 1400 | 1450 | 1500 | 1580 | 1710 | 1710 | 1930 | 2080 | 2080 | 2850 | 2920 | 3350 | 3420 | |
Height | mm | 2340 | 2450 | 2810 | 2980 | 3180 | 3180 | 3490 | 3690 | 3720 | 3850 | 3940 | 4050 | 4210 | |
Operation weight | t | 6.3 | 8.4 | 11.1 | 14 | 17 | 18.9 | 26.6 | 31.8 | 40 | 46.2 | 58.2 | 65 | 70.2 | |
Shipment weight | t | 5.2 | 7.1 | 9.3 | 11.5 | 14.2 | 15.6 | 20.8 | 24.9 | 27.2 | 38.6 | 47.8 | 55.4 | 59.8 | |
Cooling water inlet temp. range:15℃-34℃, minimum chilled water outlet temp. -2℃. Cooling capacity regulation range 10%~100%. Chilled water, cooling water and hot water fouling factor:0.086m2•K/kW. Chilled water, cooling water and hot water maximum working pressure:0.8MPa. Power type: 3Ph/380V/50Hz (or customized). Chilled water flow adjustable range 60%-120%, cooling water flow adjustable range 50%-120% Hope Deepblue reserves the right of interpretation,the parameters maybe amended at final design. |
Model | RXZ(120/68)- | 35 | 58 | 93 | 116 | 145 | 174 | 233 | 291 | 349 | 465 | 582 | 698 | 756 | |
Cooling capacity | kW | 350 | 580 | 930 | 1160 | 1450 | 1740 | 2330 | 2910 | 3490 | 4650 | 5820 | 6980 | 7560 | |
104 kCal/h | 30 | 50 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 650 | ||
USRT | 99 | 165 | 265 | 331 | 413 | 496 | 661 | 827 | 992 | 1323 | 1653 | 1984 | 2152 | ||
Chilled water |
Inlet/outlet temp. | ℃ | 12→7 | ||||||||||||
Flow rate | m3/h | 60 | 100 | 160 | 200 | 250 | 300 | 400 | 500 | 600 | 800 | 1000 | 1200 | 1300 | |
Pressure drop | kPa | 60 | 60 | 70 | 65 | 65 | 65 | 60 | 60 | 60 | 90 | 90 | 120 | 120 | |
Joint connection | DN(mm) | 100 | 125 | 150 | 150 | 200 | 250 | 250 | 250 | 250 | 300 | 350 | 400 | 400 | |
Cooling water |
Inlet/outlet temp. | ℃ | 32→38 | ||||||||||||
Flow rate | m3/h | 113 | 188 | 300 | 375 | 469 | 563 | 750 | 938 | 1125 | 1500 | 1875 | 2250 | 2438 | |
Pressure drop | kPa | 65 | 70 | 70 | 75 | 75 | 80 | 80 | 80 | 70 | 70 | 80 | 80 | 80 | |
Joint connection | DN(mm) | 125 | 150 | 200 | 250 | 250 | 300 | 350 | 350 | 350 | 400 | 450 | 500 | 500 | |
Hot water | Inlet/outlet temp. | ℃ | 120→68 | ||||||||||||
Flow rate | m3/h | 7 | 12 | 19 | 24 | 30 | 36 | 48 | 60 | 72 | 96 | 120 | 144 | 156 | |
Power Demand | kW | 3.9 | 4.1 | 5 | 5.4 | 6 | 7 | 8.4 | 9.4 | 9.7 | 11.7 | 16.2 | 17.8 | 17.8 | |
Dimension | Length | mm | 4105 | 4105 | 5110 | 5890 | 5890 | 6740 | 6740 | 6820 | 7400 | 7400 | 8720 | 9670 | 9690 |
Width | mm | 1775 | 1890 | 2180 | 2244 | 2370 | 2560 | 2610 | 2680 | 3220 | 3400 | 3510 | 3590 | 3680 | |
Height | mm | 2290 | 2420 | 2940 | 3160 | 3180 | 3240 | 3280 | 3320 | 3480 | 3560 | 3610 | 3780 | 3820 | |
Operation weight | t | 7.4 | 9.7 | 15.2 | 18.4 | 21.2 | 23.8 | 29.1 | 38.6 | 44.2 | 52.8 | 69.2 | 80 | 85 | |
Shipment weight | t | 6.8 | 8.8 | 13.8 | 16.1 | 18.6 | 21.2 | 25.8 | 34.6 | 39.2 | 46.2 | 58 | 67 | 71.2 | |
Cooling water inlet temp. range:15℃-34℃, minimum chilled water outlet temp. 5℃. Cooling capacity regulation range 20%~100%. Chilled water, cooling water and hot water fouling factor:0.086m2•K/kW. Chilled water, cooling water and hot water maximum working pressure:0.8MPa. Power type: 3Ph/380V/50Hz (or customized) Chilled water flow adjustable range 60%-120%, cooling water flow adjustable range 50%-120% Hope Deepblue reserves the right of interpretation,the parameters maybe amended at final design. |